13. Electric Services and Lifts
13.10 Lift Services - Schematic Diagrams / Schedule


Lift Schedule
| Lift No. |
1 |
2 |
| Lift type | Passage R/ cargo lift | Passage R/ disable/ fireman lift |
| Floor Served | G/F, 1/F to 11/F | G/F, 1/F to 11/F |
| Capacity ( kg/persons ) | 1350/18 for option 'A' or 1425/19 for option 'B' | 900 kg/12 persons |
| Speed ( m/s ) | 1.75 | 1.75 |
| Power system | ACVV / VVV F | ACVV / VVV F |
| Control system |
Duplex collection |
|
| Shaft Dimension ( mm ) | 2300 (W) x 2950 (D) | 2055 (W) x 2150 (D) |
| Car internal dimension ( mm ) | See remark | 1460 (W) x 1250 (D) |
| Car internal height ( mm ) | 2600 | 2600 |
| Headroom under false ceiling | 2400 | 2400 |
| Door type | 2 panels centre opening | 2 panels centre opening |
| Door size ( mm ) | 1000 (W) x 2215 (D) | 900 (W) x 2215 (H) |
| Overrun ( mm ) | 4680 | 4680 |
| Pit depth ( mm ) | 1800 | 1800 |
| Provision for disable persons | Not required | Required |
| Fireman's switch | Not required | Required |
| Full load by pass | Required | Required |
| Antinuisance | Required | Required |